DeVIce DATA Of THe 400 V DeVIceS
3.4 Device data of the 400 V devices
3.4.1 Overview of the 400 V devices
The technical data are for 2/4-pole standard motors. With other pole numbers the drive
controller must be dimensioned onto the motor rated current. Contact KEB for special or
medium frequency motors.
Device size
Housing
Rated apparent output power
Max. rated motor power
Rated output current
Output voltage
Output phases
Output frequency
Rated output overload (60s)
Rated output overload (3s)
Overcurrent
Rated switching frequency
Rated input current
Rated input voltage
Rated input voltage UL
Input voltage range
Input voltage range DC supply
Mains phases
Mains frequency
Maximum current 0 Hz / 50 Hz at f
Maximum current 0 Hz / 50 Hz at f
Maximum current 0 Hz / 50 Hz at f
Insulation resistance @ U
DC link capacity
Table 9:
Overview device data of the 400 V devices
The output frequency is to be limited in such a way that it does not exceed 1/10 of the switching frequency.
1)
Devices with higher max. output frequency are subject to export restrictions and are only available on re-
quest.
The values refer in % to the rated output current I
2)
3.4.2 rated operation
All rated values refer to a rated operation at U
an output frequency f
34
= 4 kHz
S
= 8 kHz
S
= 16 kHz
S
= 500 V
_dc
= 50 Hz.
out
/ kVA
S
out
kW
P
/
mot
/ A
I
N
U
/ V
out
/ Hz
f
1)
out
I
/ %
2)
60s
I
/ %
2)
3s
/ %
I
2)
OC
/ kHz
f
SN
I
/ A
in
/ V
U
N
/ V
U
N_UL
U
/ V
in
U
/ V
in_dc
/ Hz
f
N
I
/
215 / 300
%
out_max
/
162 / 300
I
%
out_max
/
92 / 292
I
%
out_max
R
/
iso
MΩ
C / μF
.
N
= 400 V, rated switching frequency f
N
07
09
10
2
1.8
2.8
4.0
0.75
1.5
2.2
2.6
4.1
5.8
0...U
or 0...U
/ √2
in
in_dc
3
0...599
200
250
300
8
3.6
6.0
8.0
400
480
184...550
260...750
3
50 / 60
193 / 300
155 / 300
132 / 300
103 / 275
73 / 200
50 / 163
> 15
195
195
235
SN
and