COMBICONTROL
1.5

Technical data

General
Dimensions (HxBxT)
Weight
Installation method
Grounding
Protective system (EN 60529)
Operation temperature
Storage temperature
Climatic category (EN 60721-3-3)
Environment (IEC 664-1)
Control
Operating voltage control (US)
Power input control
Digital inputs/outputs
Wiring system
Operating voltage inputs/outputs (UM)
Output current
Input voltage/current
Axis interface
Type
Connector
Cable
Speed
Use
Ethernet interfaces
Type
Connector
Speed
125 x 44 x 144 mm
approx. 260 g
35 mm Mounting rail
via terminal strip or plug-in contact
IP20
-10...45 °C (14...113 °F)
-25...70 °C (-13...158 °F)
3K3
Pollution degree 2
18...30 V DC ±0 %
3 W max.
cage-clamp terminals
18...30 V DC ±0 %
max. 0,7 A per channel, short-circuit proof,
free-wheeling diode integrated
according to IEC 61131-2 Type 1
HSP5/485
RJ-45, 8-pole, screened
Cat5, max. 100 m
38,4...250 kBaud
Connection to KEB F5 inverter/servo, process
data transmission, communication channel
IEEE802.3
10/100BaseTx
2-Port Switch
RJ-45, 8-pole, screened
10/100 MBaud
autocrossover
GB - 5