cONNecTION Of THe POWer UNIT
4.2.6.4 Motor cable length for parallel operation of motors
The resulting motor cable length for parallel operation of motors, or parallel installation
with multiple cables arises from the following formula:
resulting motor cable length = ∑single cable length x √Number of motor cables
4.2.6.5 Motor cable cross-section
The motor cable cross-section is dependent
•
•
•
•
•
4.2.6.6 Interconnection of the motor
NOTICE
NOTICE
4.2.6.7 Terminal block X1B motor connection
Figure 20:
on the characteristic of the output current (e.g. not sine-wave).
on the real effective value of the motor current.
on the cable length.
on the type of the used cable.
on the ambient conditions such as bundling and temperature.
Protect motor against voltage peaks !
Drive controllers switch at the output with dV /dt ≤ 5kV/µs. Voltage peaks
that endanger the insulation system at the motor can occur especially in
case of long motor cables (> 15 m). A motor choke, a dv/dt-filter or sine-
wave filter can be used for protection of the motor.
faulty behaviour of the motor !
The connecting-up instructions of the motor manufacturer are always
generally valid !
R
- -
++
Name
U, V, W
Terminal block X1B motor connection
U
V
W
function
Motor connection
0.5...2.5 mm² / AWG 20-14
cross-section