brAKe cONTrOL AND TeMPerATUre DeTecTION fOr K- AND A- cONTrOL
4.3.3 Operation without temperature detection
Use of the COMBIVERT without evaluation of the temperature input:
•
or
•
4.3.4 connection of a KTy sensor
NOTICE
Name
TA1 (X1C.5);
TA2 (X1C.6)
1 Connection via shield plate
Figure 26:
1)
Deactivate the evaluation (pn33 =7)
Install bridge between terminal X1C.5 and X1C.6 (dr33=1)
No protection of the motor winding in case of wrong connection.
► Operate KTY sensors in forward direction. Non-observance leads
incorrect measurement in the upper temperature range.
► KTY sensors may not be combined with other detections.
KTY84
function
Temperature sensor input
Connection of a KTY sensor for K- and A-control
If not available, place on the mounting plate.
TA1
+
TA2
①
1)
Stetting
dr33=0; KTY84/130
dr33=3; KTY83/110
67