brAKe cONTrOL AND TeMPerATUre DeTecTION fOr P- cONTrOL
4.4.2.1 Operation without temperature detection
Use of the COMBIVERT without evaluation of the temperature input:
•
or
•
4.4.2.2 Connection of a KTY sensor
NOTICE
Name
TA1 (X1C.9);
TA2 (X1C.10)
Figure 29:
Deactivate the evaluation (pn12 = 7).
Install bridge between terminal TA1 (X1C.9) and TA2 (X1C.10) (dr33 = 1).
No protection of the motor winding in case of wrong connection.
► Operate KTY sensors in forward direction. Non-observance leads
incorrect measurement in the upper temperature range.
► KTY sensors may not be combined with other detections.
+
KTY84
Connection of a KTY sensor for P-control
X1C.9 (TA1)
X1C.10 (TA2)
function
Temperature sensor input
Stetting
dr33=0; KTY84/130
dr33=3; KTY83/110
71