ED-560
Analogue outputs (as integer
Analogue outputs (as float)
Analogue type/range
Integer format
Integer format
Integer values are encoded in one of two formats, depending on the integer format setting.
"Hexadecimal" (integer format register = 0, integer format coil OFF): the output range is scaled to an
integer value ranging from 0 to 16383 (3FFF hexadecimal).
"Engineering units" (integer format register = 1, integer format coil ON): the output, in mA or V, is
scaled up to as high a power of 10 as possible while allowing the full range of values to fit in a 16-bit
integer.
Floating-point values are encoded according to the IEEE 754 standard for 32-bit floating-point numbers. Each
value takes two sequential 16-bit Modbus registers, with the least-significant bits of the 32-bit value being held
in the lower register address ("little-endian" format). Both Modbus registers must be written or read in the
same Modbus request. The units of the float values are Volts or milliAmps.
Writing values below the minimum results in the minimum output for the range being used, and writing values
above the maximum results in the maximum output for the range being used.
The type/range codes which can be set using Modbus, and the data ranges they result in, are tabulated below.
The codes are the same as for the ASCII protocol.
Type Code
Input Type
30
0 to +20mA
31
+4 to +20mA
32
0 to +10V
Ethernet Analogue DIO
Product Manual V1.2
Modbus
Modbus access
function
type
codes
Holding register
3, 6, 16
Holding register
3, 16
Holding register
3, 6, 16
Holding register
3, 6, 16
Coil
1, 5, 15
Data Format
Float engineering unit
Integer hexadecimal
Integer engineering unit
Float engineering unit
Integer hexadecimal
Integer engineering unit
Float engineering unit
Integer hexadecimal
Integer engineering unit
© Copyright Brainboxes Ltd
Logical
984 style
address
address
0x0000 – 3
40001 – 4
0x0020 – 7
40033 – 40
0x0060 – 3
40097 – 100
0x0080
40129
0x0080
00129
+ Full Scale
Minimum
20.0
0x3FFF = 16383
20000
20.0
0x3FFF = 16383
20000
10.0
0x3FFF = 16383
10000
IEC 61131
address
%MW0 – 3
%MF32 – 39
%MW96 – 99
%MW128
%M128
0.0
0
0
4.0
0
4000
0.0
0
0
Page 97 of 100