Range settings and data formats

ED-549 Analogue input type settings (rr)
Type Code
Input Type
05
±2.5V
06 or 0D
±20mA
07
+4 to +20mA
08
±10V
09
±5V
04 or 0A
±1V
03 or 0B
±500mV
0C
±150mV
1A
0 to +20mA
3A
±75mV
3B
±250mV
Ethernet Analogue DIO
Product Manual V1.3
Data Format
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
© Copyright Brainboxes Ltd
+ Full Scale
- Full Scale
+2.5000
-2.5000
+100.00
-100.00
7FFF
+20.000
-20.000
+100.00
-100.00
7FFF
+20.000
+04.000
+100.00
+000.00
FFFF
+10.000
-10.000
+100.00
-100.00
7FFF
+5.0000
-5.0000
+100.00
-100.00
7FFF
+1.0000
-1.0000
+100.00
-100.00
7FFF
+500.00
-500.00
+100.00
-100.00
7FFF
+150.00
-150.00
+100.00
-100.00
7FFF
+20.000
+00.000
+100.00
+000.00
FFFF
+75.000
-75.000
+100.00
-100.00
7FFF
+250.00
-250.00
+100.00
-100.00
7FFF
8000
8000
0000
8000
8000
8000
8000
8000
0000
8000
8000
Page 55 of 100