ED-560 Analogue input type settings (tt)
Type Code
Input Type
30
0 to +20mA
31
+4 to +20mA
32
0 to +10V

Command List

Command
%aannttccff
!aa
#**
No Response
#aa
>(Data)
#aan
>(Data)
#aan(Data)
>
$aa0Ci
!aa
$aa1Ci
!aa
$aa2
!aannttccff
$aa4
>aaS(Data)
$aa4n
!aa
$aa5
!aas
$aa5vv
!aa
$aa6
!aa(Data)
$aa6n
!aa(Data)
$aa7CiRrr
!aa
$aa7n
!aa
$aa8Ci
!aaCiRrr
$aa9nttss
!aa
$aa9nts
!aa
$aa9n
!aattss
$aaA
>(Data)
Ethernet Analogue DIO
Product Manual V1.3
Data Format
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Engineering unit
% of FSR
2's complement hex
Response
Set device configuration
Synchronised sampling
Read analogue input of all channels
Read the analogue input of one channel
Set the output value for one channel
Perform span calibration on a channel
Perform zero calibration on a channel
Read the device configuration
Read the synchronised data
Set power on value of channel n
Read the reset status
Enable/disable the channel
Read the channel enable/disable status
Read the output value for one channel
Configure the range for one channel
Read power-on value for one channel
Read the range configuration for one channel
Configure the range for one channel
Configure the range for one channel
Read the range configuration for one channel
Read the analogue inputs of all channels
© Copyright Brainboxes Ltd
+ Full Scale
20.000
+100.00
FFF
20.000
+100.00
FFF
10.000
+100.00
FFF
Description
Minimum
00.000
+000.00
000
04.000
+000.00
000
00.000
+000.00
000
Supported
Devices
All Devices
ED-549
ED-549
ED-549
ED-560
ED-549
ED-549
All Devices
ED-549
ED-560
ED-560
ED-549
ED-549
ED-560
ED-549
ED-560
ED-549
ED-560
ED-560
ED-560
ED-549