ED-560 Output Specification
The device provides four analogue output channels, each of which has a voltage output terminal and a current
output terminal. Each analogue output channel is independently configurable by software for a calibrated 0-
10V voltage output, a 0-20mA current output or a 4-20mA current output. When an output channel is
configured for voltage output then the state of the current output signal is undefined; when an output channel
is configured for current output then the state of the voltage output signal is undefined.
The voltage outputs generate voltages within 10mV of the software-programmed value (0.1% of the full-scale
range), while sourcing between -5mA and 5mA. The temperature drift of the zero output is no larger than
30µV/°C, and the temperature drift of the span is no larger than 25ppm/°C.
The current output is of the 'sink' type, and requires an external power source. The voltage of the power
source needs to be sufficient to provide at least 2.8V at the IOut terminal, up to a maximum of 30V. The
outputs sink a current within 16µA of the software-programmed value (0.1% of the full-scale range). The
temperature drift of the zero output is no larger than 0.2µA/°C, and the temperature drift of the span is no
larger than 25ppm/°C.
The settling time for output signals will depend on the load on the outputs, but in tests with an oscilloscope
probe as the load the voltage output took around 350µs to settle when moving between 1V and 9V, and the
current output took around 4µs to settle when moving between 2mA and 18mA.

Firewall Exceptions and Port Numbers

When using the ED Devices with a firewall you may need to manually add the exception entries and port
numbers to the firewall list.
Below are the default port numbers and the firewall exceptions.
Below are listed the Windows Firewall exception entries which are added by default during the installation of
Boost.IO Manager.
Brainboxes Boost.IO Suite
Brainboxes Boost.IO Suite (Device Discovery)
(Except Windows XP32 & 64 bits)
UPnP Framework (Windows XP32 & 64 bits)
Network Discovery (Windows 7 or later)
If you are using other anti-virus or firewall software you may need to add these exceptions into the anti-virus
and firewalls you have installed.
Ethernet Analogue DIO
Product Manual V1.3
Function
Default port number
Device web server
TCP port 80
ASCII protocol
TCP port 9500
Modbus protocol
TCP port 502
Firmware upgrade
UCP ports 67, 68, 69