Command to set the specified channel full scale range configuration. This is an alternative form of the
$aa9nttss command, for compatibility with software designed for other devices.
Command Syntax:
Delimiter character
$
aa
Address of the device to be configured in hexadecimal format (
9
Command to set the channel range code
Command to specify the input channel where n is the input channel number
n
Command to specify the type code where t is the second character of the type code from the
t
'Range settings and data formats' table
s
Command to specify the output slew rate – not implemented on current firmware, use a value
of 0 to ensure that the behaviour does not change when the feature is added.
Checksum, if enabled
[CS]
Carriage Return
(CR)
Response
:
!aa[CS](CR)
Valid Command:
?aa[CS](CR)
Invalid Command:
Delimiter for a valid command
!
Delimiter for an invalid command
?
Address of the device which responded
aa
Checksum
[CS]
Carriage Return
(CR)
Examples:
Send command to set the first channel to
$019020(CR)
Command:
!01(CR)
Response:
Send command to set the fourth channel to the 4-20mA range: n=3, t=1, s=0
$019310(CR)
Command:
!01(CR)
Response:
Ethernet Analogue DIO
Product Manual V1.2
$aa9nts[CS](CR)
the
0-10V range: n=0, t=2, s=0