Description:
Command to read data from all the analogue input channels.
Command Syntax:
#
Delimiter character
aa
Address of the device in hexadecimal format (
[CS]
Checksum
(CR)
Carriage Return
Response
:
>(Data)[CS](CR)
Valid Command:
?aa[CS](CR)
Invalid Command:
>
Delimiter for a valid command
?
Delimiter for an invalid command
(Data)
Data from the analogue input channels
aa
Address of the device which responded
[CS]
Checksum
(CR)
Carriage Return
Examples:
Read the analogue values of the all the lines with the data format set to engineering unit.
#01(CR)
Command:
>+00.156+00.165-00.038+00.049+00.078+00.111+00.015+00.004(CR)
Response:
Read the analogue values of all the lines with the data format set to % of full scale range.
#01(CR)
Command:
>+000.69-001.39+002.30+004.59+009.17+023.14-046.10+092.00(CR)
Response: