Selection List Of Binary Signals For Digital Inputs (Din) - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
Signal
FQM end pos. CL
FQM FS diag. result
FQM timeout winding
FQM timeout limit
FQM fault temp.-volt.
FQM fail safe flt
FQM timeout motor
Maintenance reminder
MPV/LPV pos. reached
Disabled
Runs_OP/CL+blinker
17.2.

Selection list of binary signals for digital inputs (DIN)

Conditions:
Table 29:
Signal
Not used
MODE
OPEN
CLOSE
STOP
RESET
I/O interface
OPEN / CLOSE
Description
FQM has reached end position CLOSED at the output drive side.
The result of the diagnostics via winding switch is available as fault.
Winding was not completed within the permissible initialisation time of 2.5 minutes.
The end position switch was not active within the permissible waiting time of 10 seconds.
The permissible tolerance range for the internal temperature or the voltage range of the respective FQM
unit was fallen short of or exceeded or the permissible tolerance range for 24 V DC at ESD input was
fallen short of or exceeded for a duration of minimum 1 second.
The signal is generated if one of the following conditions applies:
FQM FS-ESD request not active AND FQM timeout winding or FQM timeout limit or FQM timeout
motor active
FQM FS-ESD request not active AND FQM FS ready active AND FQM FS-PosOk not active
FQM FS-ESD request not active AND FQM FS ready not active AND FQM FS-PosOk active
FQM FS-ESD request not active AND FQM fail safe ini. executed AND (FQM FS-PosOk not active
OR FQM FS ready not active)
FQM FS-ESD request active AND FQM FS ready active
The electric motor does not rotate during an initialisation operation.
This signal will be activated if at least on the lifetime accounts (in %) has passed the activation threshold
configured for this signal.
This signal can be configured (parameter Maintenance required M0871) and comprises a combination
of the following signals:
Mainten. mechanics
LPV SA-CLOSE
Mainten. lubricant
Mainten. contactors
Mainten. interval
MPV (Multiport Valve)/LPV (Lift Plug Valve) position reached.
The operation via the push buttons on the local controls is disabled.
The actuators runs while the indication light for the respective direction of operation (OPEN/CLOSE) is
blinking simultaneously at local controls.
<Additional inputs> or additional <Parallel interface>
Depending on the version, the actuator controls are equipped with up to 10 digital
inputs.
The inputs are designed for binary signals (standard input level: +24 V DC) and can
be used, for example, to receive operation commands OPEN, STOP, CLOSE, to
control intermediate positions or for the EMERGENCY signal.
Configuration of digital inputs
Required user level: Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Description
Input not assigned
Change-over between OPEN - CLOSE control and setpoint control
Operation command OPEN
Operation command CLOSE
Operation command STOP
Reset fault signal
Change-over between fieldbus interface and parallel interface
Operation command OPEN/CLOSE for two-wire control