Rate Time Td: Set; Actual Value Source (Input For Actual Process Value); Stepping Mode - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
8.5.10.

Rate time Td: set

Information
8.5.11.

Actual value source (input for actual process value)

I/O interface
Fieldbus interface
8.6.

Stepping mode

Conditions
Characteristics
Reset time Ti M0745
Default value: 1,000 s (seconds)
Setting range: 1 ... 1000 s
The rate time determines the D portion of the controller. Typically, no setting is
required here (= 0), since actuator and valve
react abruptly to a sudden occurrence of an error variable.
Increase Td in case of propensity for oscillation.
Initial value for actuators: 0 s
Customer settings M0041
Process controller M0742
Rate time Td M0746
Default value: 0 s (seconds)
Setting range: 1 ... 100 s
Customer settings M0041
Process controller M0742
Actual value source M0756
Default value: I/O interface
Setting values:
The actual process value is defined via an analogue input (AIN 1 or AIN 2) of the
I/O interface.
The actual process value is defined via the fieldbus.
This function requires one of the following equipments within the actuator:
Electronic control unit (non-intrusive version)
Potentiometer
Electronic position transmitter EWG/RWG
With stepping mode, the operating time can be increased for the entire or any
portion of the valve travel.
Stepping mode can be individually activated for the directions OPEN and
CLOSE.
Application functions
due to the operating time
cannot
61