Off Times For Intermediate Positions (Pivot Points): Set; Two-Wire Control - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Application functions
Off time in OPEN
Off time in CLOSED
Off time in OPEN & CL.
Information
8.2.3.

Off times for intermediate positions (pivot points): set

8.3.

Two-wire control

Conditions
Characteristics
Information
Default setting
50
Actuator stops at pivot point during operation in direction OPEN. If an operation
command in direction OPEN is present at the end of the pause time, the actuator
resumes operation into direction OPEN. If an operation command in direction CLOSE
is present during the pause time, the pause is aborted and operation into direction
CLOSE resumed.
When reaching the pivot point, the actuator stops during operation in direction CLOSE.
If an operation command in direction CLOSE is present at the end of the pause time,
the actuator resumes operation into direction CLOSE. If an operation command in
direction OPEN is present during the pause time, the pause is interrupted and
operation into direction OPEN resumed.
Actuator stops automatically upon reaching the pivot point. If an operation command
in direction OPEN or CLOSE is present at the end of the pause time, the actuator
resumes operation depending on the operation command.
The actuator stops for each activated intermediate position for which operation be-
haviour Stop in OPEN, Stop in CLOSED or Stop in OPEN & CL. is assigned.
An off time can be defined for each pivot point.
If a pivot point is reached with the operation behaviour Off time in OPEN, Off time
in CLOSED or Off time in OPEN & CL., the actuator controls generate a signal during
off time:Operation pause active
Required user level: Specialist (4) or higher.
Customer settings M0041
Intermediate positions M0143
Off times M0268
Off time 1 M0285
Default values: 00:01.0 min:s (1 second)
Setting ranges: 00:00.2 ... 30:00.0 min : s (0.2 seconds
<Additional inputs> or additional <parallel interface>
Operation mode Remote (Selector switch = position Remote control).
With the <Two-wire control> function, the actuator can be operated to end position
OPEN or CLOSED via one digital input.
In this function, the actuator only reacts to commands via the input OPEN / CLOSE.
Other inputs to which the operation commands OPEN, STOP, CLOSE were assigned,
do not have any function.
Execute operation commands via digital input:
Designation of digital input OPEN / CLOSE
(Wiring diagram designation:
Input OPEN / CLOSE = low level (0 V DC or input open):
Actuator runs in direction CLOSE.
Input OPEN / CLOSE = high level (standard: +24 V DC):
Actuator runs in direction OPEN.
Configuration of digital input
For the two-wire control, a digital input for the OPEN / CLOSE signal has to be
configured.
Required user level: Specialist (4)
Device configuration M0053
I/O interface M0139
Digital inputs M0116
AC 01.2/ACExC 01.2 Profinet
OPEN/CLOSE
Actuator controls
30 minutes)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acexc 01.2

Table of Contents