Monitoring functions
No cut-off
Cut-off
10.6.
Motion detector
Requirements
Characteristics
Information
10.6.1.
Activate motion detector
Function not active
Function active
10.6.2.
Detection time dt
100
in selector switch position Remote control (REMOTE):
-
Via fieldbus, Reset command, byte 1 bit 3 of output data if fieldbus is the
active command source.
-
Or via a digital input (I/O interface) with RESET command if a digital input
is configured for RESET signal and the I/O interface is the active command
source.
In case of operation from an intermediate position, reaction monitoring will only be
performed if the actuator is equipped with position feedback function.
Activate switching off for reaction time error
Required user level: Specialist (4) or higher.
Customer settings M0041
Reaction monitoring M0632
Actuator behaviour M0633
Default value: No cut-off
Setting values:
The reaction monitoring only issues a warning.
The reaction monitoring issues a fault signal, the actuator is stopped.
Set reaction time
Customer settings M0041
Reaction monitoring M0632
Reaction time M0634
Default value: 15.0 s
Setting range: 15.0 ... 300.0 seconds (0 seconds up to 5 minutes)
Position transmitter in the actuator.
The motion detector checks whether the actuator moves even without operation
command (e.g. in manual operation or if there is no self-retaining).
Controls identify motion if the actuator moves more than the pre-set travel difference
within the predefined recording time. Controls signal: Output drive rotates
Parameters for motion detection have a direct impact on reaction monitoring.
Required user level: Specialist (4) or higher.
Customer settings M0041
Motion detector M0676
Motion detector M0675
Default value: Function active
Setting values:
Monitoring is deactivated.
Monitoring is activated.
Required user level: Specialist (4) or higher.
Customer settings M0041
Motion detector M0676
Detect. time dt M0677
Detect. time dt (MWG) M0681
Actuator controls
AC 01.2/ACExC 01.2 Profinet