Corrective Action; Primary Fuses; Fault Indications And Warning Indications - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
16.

Corrective action

16.1.

Primary fuses

16.2.

Fault indications and warning indications

Table 22:
Faults and warnings via status indications in the display
Indication on display
S0001
S0005
Warnings
S0006
Not ready REMOTE
S0007
Fault
S0008
Out of specification
S0009
Function check
S0010
Maintenance required
S0011
Failure
The actuator controls have to be opened to exchange the primary fuses. For detailed
information, refer to operation instructions for actuator.
Faults interrupt or prevent the electrical actuator operation. In the event of a fault,
the display backlight is red.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes. The display remains white.
Collective signals include further indications. They can be displayed via the
Details push button. The display remains white.
Description/cause
Instead of the valve position, a status text is dis-
played.
Collective signal 02:
Indicates the number of active warnings.
Collective signal 04:
Indicates the number of active signals.
Collective signal 03:
Indicates the number of active faults.
The actuator cannot be operated.
Collective signal 07:
Indication according to NAMUR recommendation
NE 107
Actuator is operated outside the normal operation
conditions.
Collective signal 08:
Indication according to NAMUR recommendation
NE 107
The actuator is being worked on; output signals are
temporarily invalid.
Collective signal 09:
Indication according to NAMUR recommendation
NE 107
Recommendation to perform maintenance.
Collective signal 10:
Indication according to NAMUR recommendation
NE 107
Actuator function failure, output signals are invalid
Corrective action
Remedy
For a description of the status texts, refer to <Status
texts in Menu S0001>.
For indicated value > 0: Press push button
tails.
For details, refer to <Warnings and Out of specific-
ation> table.
For indicated value > 0: Press push button
tails.
For details, refer to <Not ready REMOTE and
Function check> table.
For indicated value > 0: Press push button
to display a list of detailed indications.
For details, refer to <Faults and Failure> table.
For indicated value > 0: Press push button
tails.
For details, refer to <Warnings and Out of specific-
ation> table.
For indicated value > 0: Press push button
tails.
For details, refer to <Not ready REMOTE and
Function check> table.
For indicated value > 0: Press push button
to display a list of detailed indications.
For indicated value > 0: Press push button
to display a list of detailed indications.
For details, refer to <Faults and Failure> table.
De-
De-
Details
De-
De-
Details
Details
135

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acexc 01.2

Table of Contents