Actuator controls
AC 01.2/ACExC 01.2 Profinet
9.9.6.
PVST monitoring time: set
9.9.7.
PVST operating time: set
9.9.8.
PVST reversing time: set
9.9.9.
PVST reminder
Function not active
Function active
PVST stroke M0854
Default value: 10.0 %
Setting range: 0.0 ... 100.0 %
The actuator remains in the current position if the test could not be completed within
the pre-set time.
Customer settings M0041
PVST M0852
PVST monitoring M0855
Default value: 01:00.0 min:s (1 minute)
Setting range: 00:01.0 ... 50:00.0 min:s (minutes:seconds)
During operating time controlled PVST execution (parameter PVST operation mode
M0889 = End position test), this parameter determines the permissible PVST
operating time.
Customer settings M0041
PVST M0852
PVST operating time M0890
Default value: 00:02.0 min:s (2 seconds)
Setting range: 00:00.1 ... 15:00.0 min:s (minutes:seconds)
Waiting time during PVST prior to returning to initial position.
Customer settings M0041
PVST M0852
PVST reversing time M0891
Default value: 00:02.0 min:s (2 seconds)
Setting range: 00:00.1 ... 15:00.0 min:s (minutes:seconds)
If this function is active, a signal is generated if no PVST was executed during the
reminder period.
Activate reminder
Required user level: Specialist (4) or higher.
Customer settings M0041
PVST M0852
PVST reminder M0892
Default value: Function not active
Setting values:
Reminder not activated.
Reminder activated.
Set reminder period
Customer settings M0041
PVST M0852
PVST reminder period M0893
Default value: 0 d
Failure functions
91