Temperature Monitoring; Heater System/Heater Monitoring - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Monitoring functions
On
Function not active
On
10.8.

Temperature monitoring

Characteristics
Conditions:
Information
10.9.

Heater system/heater monitoring

Function not active
Function active
102
Monitoring is activated. Should the auxiliary voltage 24 V DC for supplying the control
inputs fail, a warning will be issued.
Activate monitoring of external supply 24 V DC
Required user level: Specialist (4).
Device configuration M0053
Monitoring function M0645
Monitor 24 V DC ext. M0649
Default value: Function not active
Setting values:
Monitoring is deactivated.
Monitoring is activated. Should the external supply 24 V DC fail, a warning will be
issued.
If the respective sensors are installed in the devices, the actuator controls monitor
different temperatures.
If certain temperature limits are exceeded or fallen short of, the controls either send
a warning or a fault signal.
For temperature within the control unit of the actuator: MWG (magnetic limit
and torque transmitter)
For motor temperature: additionally temperature sensor (PT 100) in the motor
For gear housing temperature: additionally temperature sensor (PT 100) in the
gearing
Current device temperatures can also be displayed. Refer to <Display device tem-
peratures>.
The heater system within the actuator controls housing and the heater on the control
unit (within the switch compartment of the actuator) can be monitored. If the monitoring
is activated the following warning will be generated if the heater system or the heater
(circuit = interrupted) fails:
In the display of the local controls, status indication S0005 Warnings
-
Details: Internal warning Wrn heater
Via fieldbus: Wrn heater
For further information on the heater system and the heater refer to separate <Heater
system and heater> chapter.
Activate heater system monitoring
Heater system monitoring monitors all connected heaters for failure.
Required user level: Specialist (4).
Device configuration M0053
Monitoring function M00645
Monitor heat. system M0647
Default value: Function not active
Setting values:
Heater monitoring is deactivated.
Heater monitoring is activated.
Actuator controls
AC 01.2/ACExC 01.2 Profinet

Advertisement