Signal Range Of Analogue Output 1 - AUMA AC 01.2 Manual

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
Torque
Input AIN 1
Input AIN 2
Fieldbus AOUT 1
Fieldbus AOUT 2
Temp. ctrls norm. ‰
Temp. ctrl unit norm ‰
5.4.2.

Signal range of analogue output 1

0 - 20 mA
4 - 20 mA
20 - 0 mA
20 - 4 mA
X to Y mA
For torque seating, the end positions OPEN and CLOSED of the limit switching
should be set as close as possible to the end positions of the valve to minimise the
deviation of the feedback.
Torque feedback E6
Condition: MWG position transmitter in actuator.
The zero point is in the centre of the selected output range (10 mA or 12 mA). The
torque in direction CLOSE is indicated with 0
direction OPEN with 10 20 mA or 12 20 mA. For 127 % of the maximum nominal
output torque, 0 or 4 mA are indicated in direction CLOSE, and 20 mA are indicated
in direction OPEN.
Figure 30: Actual torque value
127 %= maximum nominal torque in end position CLOSED reached
+127 %= maximum nominal torque in end position OPEN reached
Analogue value transmitted via AIN1 (refer to wiring diagram) to the actuator.
Condition: An analogue signal (e.g. 0
AIN 1.
Analogue value transmitted via AIN 2 (refer to wiring diagram) to the actuator.
Condition: An analogue signal (e.g. 0
AIN 2.
Analogue value transmitted from the fieldbus to the actuator.
The value is transmitted via fieldbus in per mil (value: 0
continuous value. e.g 4 to 20 mA, via output Signal AOUT 1.
If another analogue value is transmitted via fieldbus to the actuator, it can be sent
as continuous value. e.g 4 to 20 mA, via output Signal AOUT 2.
Actuator controls temperature (normalised) in per mil.
Condition: MWG position transmitter in actuator.
Control unit temperature (normalised) in per mil.
Condition: MWG position transmitter in actuator.
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Signal range AOUT1 M0129
Default value: 0 - 20 mA
Setting values:
Analogue output 1 generates a 0
Analogue output 1 generates a 4
Analogue output 1 generates a 20
Analogue output 1 generates a 20
The signal range (X-Y) of the analogue output can be freely configured using two
parameters.
10 mA or 4
20 mA) is connected to the analogue input
20 mA) is connected to the analogue input
1000) and can be sent as
20 mA signal.
20 mA signal.
0 mA signal.
4 mA signal.
Signals (output signals)
12 mA, the torque in
27