AUMA AC 01.2 Manual page 141

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Actuator controls
AC 01.2/ACExC 01.2 Profinet
Individual indications
Indication on display
24 V DC customer
24 V DC internal
Wrn res. data in use
Wrn ref.actual position
Wrn range act.pos.
Wrn sign.loss act.pos.
Wrn event mark
Wrn Tm mark
Config. error REMOTE (Collective signal 22)
IE I/O interface
IE remote interface
IE remote Prm Config
FQM collective fault (Collective signal 25)
FQM FS diag. result
FQM timeout winding
FQM timeout limit
FQM fault temp.-volt.
FQM fail safe flt
FQM timeout motor
Table 27:
Status texts in menu S0001
Indication on display
Sensor failure
Not referenced
Calibration
Out of range
Remedy
The 24 V DC customer auxiliary supply to control the digital inputs has failed.
Check 24 V DC inputs (DIN).
The internal 24 V DC power supply of the controls used to provide the electronics components (sub-
assemblies within the AC 01.2 controls and in the actuator) has exceeded the power supply limits .
Check internal 24 V DC voltage supply.
Reboot AUMATIC.
Operate actuator fully in end positions OPEN and CLOSED.
Verify primary reduction gearing settings within the actuator.
Check position feedback.
Check system configuration.
Check system configuration.
Check I/O interface M0139 parameter. The setting must correspond to the wiring diagram.
Check wiring.
Check I/O interface.
Check configuration.
Check configuration.
The result of the diagnostics via winding and blinker transmitter switch is available as fault.
Winding was not completed within the permissible initialisation time of 2.5 minutes.
The end position switch was not active within the permissible waiting time of 10 seconds.
The permissible tolerance range for the room temperature or the voltage range of the respective FQM
unit was fallen short of or exceeded or the permissible tolerance range for 24 V DC at ESD input was
fallen short of or exceeded for a period of minimum 1 second.
The signal is generated if one of the following conditions applies:
FQM FS-ESD request not active AND FQM timeout winding or FQM timeout limit or FQM timeout
motor active
FQM FS-ESD request not active AND FQM FS ready active AND FQM FS-PosOk not active
FQM FS-ESD request not active AND FQM FS ready not active AND FQM FS-PosOk active
FQM FS-ESD request not active AND FQM fail safe ini. executed AND (FQM FS-PosOk not active
OR FQM FS ready not active)
FQM FS-ESD request active AND FQM FS ready active
The electric motor does not rotate during an initialisation operation.
Description/cause
Hardware is either defective or not available:
for potentiometer, RWG, EWG = signal loss
for MWG = calibration active or Hall sensor de-
fective
For potentiometer, RWG, EWG: end positions not
set
Calibration active
Outside the value range
for potentiometer = insufficient stroke between
the set end positions
for RWG, EWG = end position OPEN = end
position CLOSED
for MWG = excessive stroke between the set
end positions
Remedy
Check or replace hardware.
Set end positions and perform reference operation.
Set valid stroke.
Corrective action
141

Advertisement

Table of Contents
loading