AUMA AC 01.2 Manual page 138

Actuator controls
Hide thumbs Also See for AC 01.2:
Table of Contents

Advertisement

Corrective action
Faults and Failure
Indication on display
Thermal fault
Fault no reaction
Poti Out of Range
1)
LPV not ready
Wrn input AIN 1
Wrn input AIN 2
Incorrect rotary direct.
2)
FQM collective fault
1)
For lift plug valve product variant
2)
For actuators equipped with fail safe unit
Table 25:
Not ready REMOTE and Function check (collective signal 04)
Indication on display
Wrong oper. cmd
Sel. sw. not REMOTE
Service active
Disabled
EMCY stop active
EMCY behav. active
I/O interface
Handwheel active
138
Description/cause
Motor protection tripped
No actuator reaction to operation commands within
the set reaction time.
Potentiometer is outside the permissible range.
LPV: Lift Plug Valve function
The master actuator signals a fault
Loss of signal analogue input 1
Loss of signal analogue input 2
Contrary to the configured direction of rotation and
the active operation command, the motor turns into
the wrong direction.
Collective signal 25:
Description/cause
Collective signal 13:
Possible causes:
Several operation commands (e.g. OPEN and
CLOSE simultaneously, or OPEN and SET-
POINT operation simultaneously)
A setpoint is present and the positioner is not
active
Selector switch is not in position REMOTE.
Operation via service interface (Bluetooth) and
AUMA CDT service software.
Actuator is in operation mode Disabled.
The EMERGENCY stop switch has been operated.
The motor control power supply (contactors or
thyristors) is disconnected.
Operation mode EMERGENCY is active (EMER-
GENCY signal was sent).
0 V are applied at the EMERGENCY input.
The actuator is controlled via the I/O interface (par-
allel).
Manual operation is activated.
Actuator controls
AC 01.2/ACExC 01.2 Profinet
Remedy
Cool down, wait.
If the fault indication display persists after cool-
ing down:
-
Set selector switch to position Local con-
trol (LOCAL) and reset fault indication via
push button RESET.
-
Execute reset command via fieldbus.
Check fuses.
Check movement at actuator.
Check device configuration:
Parameter Low limit Uspan M0832 must be less
than parameter Volt.level diff. potent. M0833.
Check wiring.
Check wiring.
Check operation command control.
For 3-phase AC current mains, activate phase
monitoring (parameter Adapt rotary dir. M0171).
Check device configuration setting (parameter
Closing rotation M0176).
To delete the fault indication: Disconnect actuator
controls from the mains and perform reboot.
Press push button
Details to display a list of indi-
vidual indications.
For a description of the individual signals, refer to
<Individual signals> table/ Configuration error (col-
lective signal 11).
Remedy
Check operation commands (reset/clear all op-
eration commands and send one operation
command only).
Set parameter Positioner to Function active.
Check setpoint.
Press push button
Details to display a list of indi-
vidual indications.
For details, refer to <Individual indications> table.
Set selector switch to position REMOTE.
Exit service software.
Check setting and status of function <Local controls
enable>.
Enable EMERGENCY stop switch.
Reset EMERGENCY stop state by means of
Reset command.
Detect cause for EMERGENCY signal.
Verify failure source.
Apply +24 V DC at EMERGENCY input.
Check I/O interface.
Start motor operation.