Status [720] - Omron SX-F Instruction Manual

High power direct torque control inverters
Table of Contents

Advertisement

View Operation/Status [700]

11-7-2 Status [720]

VSD Status [721]
Indicates the overall status of the variable speed drive.
721 VSD Status
Stp 1/222/333/44
Fig. 110 VSD status
Display position
1
222
333
44
Example: "A/Key/Rem/TL"
This means:
A: Parameter Set A is active.
Key: Reference value comes from the keyboard (CP).
Rem: Run/Stop commands come from terminals 1-22.
TL: Torque Limit active.
Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Fieldbus format
Modbus format
Description of communication format
Integer values and bits used
Bit
Integer representation
1-0
Active Parameter set, where 0=A, 1=B, 2=C, 3=D
4-2
Source of Reference control value, where 0=Rem, 1=Key, 2=Com, 3=Option
Source of Run/Stop/Reset command, where 0=Rem, 1=Key, 2=Com,
7-5
3=Option
15-8
Active limit functions, where 0=No limit, 1=VL, 2=SL, 3=CL, 4=TL
Status
Parameter Set
A,B,C,D
-Key (keyboard)
-Rem (remote)
Source of reference
-Com (Serial comm.)
value
-Opt (option)
-Key (keyboard)
-Rem (remote)
Source of Run/Stop/
-Com (Serial comm.)
Reset command
-Opt (option)
-TL (Torque Limit)
-SL (Speed Limit)
Limit functions
-CL (Current Limit)
-VL (Voltage Limit)
- - - -No limit active
31015
121/159
23f7
UInt
UInt
Section 11-7
Value
245