View Trip Log [800]; Trip Message Log [810] - Omron SX-F Instruction Manual

High power direct torque control inverters
Table of Contents

Advertisement

View Trip Log [800]

11-8 View Trip Log [800]

11-8-1 Trip Message log [810]

Main menu with parameters for viewing all the logged trip data. In total the
VSD saves the last 10 trips in the trip memory. The trip memory refreshes on
the FIFO principle (First In, First Out). Every trip in the memory is logged on
the time of the Run Time [731] counter. At every trip, the actual values of sev-
eral parameter are stored and available for troubleshooting.
Display the cause of the trip and what time that it occurred. When a trip occurs
the status menus are copied to the trip message log. There are nine trip mes-
sage logs [810]–[890]. When the tenth trip occurs the oldest trip will disap-
pear.
After reset of occurred trip, the trip message will be removed and menu [100]
will be indicated.
Unit:
Range:
For fieldbus integer value of trip message, see message table for warnings,
[722].
Note Bits 0–5 used for trip message value. Bits 6–15 for internal use.
Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Fieldbus format
Modbus format
Trip message [811]-[81O]
The information from the status menus are copied to the trip message log
when a trip occurs.
Copied
Trip menu
from
811
711
812
712
813
712
814
714
815
715
816
716
817
717
818
718
819
719
81A
71A
81B
71B
81C
721
8x0 Trip message
Stp
h:mm:ss
h: m (hours: minutes)
0h: 0m–65355h: 59m
810 Ext Trip
Stp
132:12:14
31101
121/245
244d
UInt
UInt
Description
Process Value
Speed
Torque
Shaft Power
Electrical Power
Current
Output voltage
Frequency
DC Link voltage
Heatsink Temperature
PT100_1, 2, 3
VSD Status
Section 11-8
253