I/Os and Virtual Connections [500]
AnIn1 Function Value Min [5135]
With AnIn1 Function ValMin you define a user-defined value for the signal.
Only visible when user-defined is selected in menu [5134].
Default:
Range:
Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Fieldbus format
Modbus format
AnIn1 Function Max [5136]
With AnIn1 Function Max the physical maximum value is scaled to selected
process unit. The default scaling is dependent of the selected function of
AnIn1 [511]. See Table 26.
Default:
Min
0
Max
1
User-defined
2
Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Fieldbus format
Modbus format
AnIn1 Function Value Max [5137]
With AnIn1 Function VaMax you define a user-defined value for the signal.
Only visible when user-defined is selected in menu [5136].
Default:
Range:
5135 AnIn1 VaMin
Stp
0.000
A
0.000
-10000.000 – 10000.000
43541
170/190
4dd5
Long,
Speed 1=1 rpm
Torque 1=1%
Process val 1=0.001
EInt
5136 AnIn1 FcMax
Stp
Max
A
Max
Min value
Max value
Define user value in menu [5137]
43207
169/111
4c87
Long,
Speed/Torque 1=1 rpm or %.
Other 1= 0.001
EInt
5137 AnIn1 VaMax
Stp
0.000
A
0.000
-10000.000 – 10000.000
Section 11-5
193