I/Os and Virtual Connections [500]
204
Fieldbus format
Modbus format
AnOut1 Bipol [5333]
Automatically displayed if User Bipol mA or User Bipol V is selected in menu
AnOut1 Setup. The menu will automatically show mA or V range according to
the selected function. The range is set by changing the positive maximum
value; the negative value is automatically adapted accordingly. Only visible if
[512] = User Bipol mA/V.
Default:
Range:
Communication information
Modbus Instance no/
DeviceNet no:
Profibus slot/index
EtherCAT index (hex)
Fieldbus format
Modbus format
AnOut1 Function Min [5334]
With AnOut1 Function Min the physical minimum value is scaled to selected
presentation. The default scaling is dependent of the selected function of
AnOut1 [531].
Default:
Min
0
Max
1
User-defined
2
Table 28 shows corresponding values for the min and max selections depend-
ing on the function of the analogue output [531].
Table 28
AnOut Function
Process Value
Speed
Torque
Process Ref
Shaft Power
Frequency
Current
El Power
Output Voltage
DC voltage
AnIn1
AnIn2
AnIn3
AnIn4
Long, 1=0.01
EInt
5333 AnOut1Bipol
Stp -10.00-10.00V
-10.00–10.00 V
-10.00–10.00 V, -20.0–20.0 mA
43255
169/159
4cb7
Long, 1=0.01
EInt
5334 AnOut1FCMin
Stp
Min
A
Min
Min value
Max value
Define user value in menu [5335]
Min Value
Process Min [324]
Min Speed [341]
0%
Process Min [324]
0%
0 Hz
0 A
0 W
0 V
0 V
AnIn1 Function Min
AnIn2 Function Min
AnIn3 Function Min
AnIn4 Function Min
Section 11-5
Max Value
Process Max [325]
Max Speed [343]
Max Torque [351]
Process Max [325]
Motor Power [223]
Motor Frequency [222]
Motor Current [224]
Motor Power [223]
Motor Voltage [221]
1000 V
AnIn1 Function Max
AnIn2 Function Max
AnIn3 Function Max
AnIn4 Function Max