DDMC Analog Input Process Meter / Controller

Panel Mounting Instructions

Prepare a standard 1/8 DIN panel cutout -
3.622" x 1.772" (92 mm x 45 mm). Refer to

Figure 1. 1/8 DIN Panel Cutout Dimensions

below for more details.
Clearance: allow at least 6.0" (152 mm) behind
the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to
maintain Type 4X rating: 0.06" (1.5 mm) steel
panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with
the meter (back-off the two screws so that there is
¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws
against the panel. To achieve a proper seal,
tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side.
DO NOT OVER TIGHTEN, as the rear of the
panel may be damaged.
3.622" (92 mm)
Square Corners to 0.060"
(1.5mm) Max Radius
B
1.772"
Panel Cutout
(45mm)
to DIN 43700
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Figure 1. 1/8 DIN Panel Cutout Dimensions
DO NOT apply AC or DC power to the meter when using the
Micro USB connection.

Figure 2. Panel Mounting Details