Setting The Display Parameter & Intensity (Dsplay); Display Intensity (D-Inty) - Ametek DDMC Instruction Manual

Analog input process meter / controller
Table of Contents

Advertisement

DDMC Analog Input Process Meter / Controller
Setting the Display Parameter &
Intensity (dsplay)
The main display (Line 1) can be programmed to
display:
1.
Process value 1 (PV1)
2.
Process value 2 (PV2)*
3.
Percent of PV1 (PCT)*
4.
Relay set points
5.
Max & min values
6.
Modbus input
7.
Display reading and units
8.
Display gross
9.
Toggle net & gross
The secondary display (Line 2) can be programmed
to display:
1.
Unit
2.
Process value 1 (PV1)
3.
Process value 2 (PV2)*
4.
Percent of PV1 (PCT)*
5.
Relay set points
6.
Max & min values
7.
Engineering units or custom legends
8.
Modbus input
9.
Off (no display)
10. Toggle reading and units
11. Display gross
12. Toggle net/gross
*These menu items will only appear if Dual-Scale
feature is turned on.
After setting up the input and display, press the Menu
button to exit programming and skip the rest of the
setup menu. Press the Menu button again and the Up
arrow to reach the Program menu and complete the
scaling or calibration of the meter.

Display Intensity (d-Inty)

The meter has eight display intensity levels to give the
best performance under various lighting conditions.
Select intensity 8 for outdoor applications. The default
intensity is 6.
Display Toggling Between Reading
& Units with Tag
The DDMC can be programmed so that line 1 toggles
between the reading and units and line 2 displays a
tag. For instance, line 1 toggles between 9500 and
Gal and line 2 displays Tank 1.
Display Parameter Menu
Dual-Scale Display Feature
The dual-scale feature is of particular value in level
applications where a second scaled display can
represent the measured input in a different form
(i.e. gallons & height). Both displays are
independently scaled and are based on the 4-20 mA
input signal.
26
Instruction Manual