DDMC Analog Input Process Meter / Controller

Setting Numeric Values

The numeric values are set using the Right and Up
arrow buttons. Press Right arrow to select next digit
and Up arrow to increment digit value. The digit being
changed is displayed brighter than the rest. Press and
hold Up to auto-increment the display value. If
negative numbers are allowed, the first digit position
will include a negative symbol (-) after the 9.
Press the Enter button, at any time, to accept a
setting or Menu button to exit without saving changes.

Setting Up the Meter (setup)

The Setup menu is used to select:
1.
Input signal the meter will accept
2.
Dual-scale feature for some level
applications
3.
Select the display units/tags
4.
Decimal point position
5.
Programming Menu
6.
Display parameter and intensity
7.
Relay operation
8.
4-20 mA analog output scaling
Press the Enter button to access any menu or press
Up arrow button to scroll through choices. Press the
Menu button to exit at any time.

Setting the Input Signal (Input)

Enter the Input menu to set up the meter to display
current (nmA) or voltage (Volt) inputs.
The current input is capable of accepting any signal
from 0 to 20 mA. Select current input to accept
0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal
from -10 to +10 VDC. Select voltage input to accept
0-5, 1-5, 0-10, or ±10 VDC signals.
After selecting mA or Volt input, d-SCAL is displayed;
press Enter to select "Yes" or "No". Selecting "Yes"
enables the dual-scale feature, which allows for the
Scale (SCALE) and Units (units) menus to be used to
scale the same input in two different scales for PV1 &
PV2.
Set d-SCAL to no if only one scale is needed for the
input.