Cooling Adjustmen; Dhw Time Program; Timer Dhw Return; Heating Circuits Time Setting - Siemens TUTORbit POL687 Instructions For Installation, Use And Maintenance Manual

Cascade sequence, heating and cooling system controller
Table of Contents

Advertisement

6 - USE

6.7 - Cooling adjustmen

To deactivate or set the cooling to zones "n" (intended as "n" of
any of the 5 zones) automatically (operation according to the
time bands) or manually (operation at constant temperature)
set Parameters-> Zones -> Zone n -> Action = Off or
Automatic or Manual.
If a QMX3 room sensor is present, this Action parameter is not
present and the Off or Automatic action must be performed
directly on the room sensor.
When the Action parameter is set in Manual, the supply
temperature to Zone "n" is performed on Parameters-> Zones
-> Cool Supply Setp.
o adjust the compensation reduction in Zone "n", edit the
Parameters->Zones->Cool Night setback.
Select the required outdoor reset for Zone "n" with the
Parameters->Zones->Cooling Outdoor reset control, then
set the curve parameters as shown in Section 4.11.
Set the time programme for heating Zone "n" with the
Parameters->Zones->Cool Timer Program control, then
set the parameters as shown in Section 6.10.

6.8 - DHW time program

TutorBit is able to set a programme on 3 daily time slots. Open
the Parameters->DHW->Time Programme-> menu
The menu displays the following parameters, in order:
Reset=Yes. to reset the time programme;
Copy=Yes to copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday (example);
and the one you want to copy the programme on:
To: Tuesday (example);
For programming, enter the start and end times of each time
slot.
If the time slots are different for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the first day,
you can use the "Copy" command to copy them to the other
days, as explained above.
Once the time programme is completed, simply activate it
by setting Parameters->DHW->DHW action = Automatic.

6.9 - Timer DHW return

Set the timer DHW return by opening the menu Parameters-
>DHW->Timer DHW return->.
The menu displays the following parameters, in order:
Reset=Yes to reset the time programme;
Copy=Yes o copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday (example);
and the one you want to copy the programme on:
To: Tuesday (example);
For programming, enter the start and end times of each time
slot.
If the time slots are different for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the first day,
you can copy the others, as explained above.
TUTORBIT

6.10 - Heating circuits time setting

For the heating circuits time setting, open the Parameters-
>Zones->Programme-> menu
Reset=Yes to reset the time programme set;
Copy=Yes to copy the programme from one day to another.
To copy, you need to indicate the programmed day:
From: Monday (example);
and the one you want to copy the programme on:
To: Tuesday (example);
For programming, enter the start and end times of each time
slot.
If there is no room sensor, the selectable time bands are:
Comfort (on) or Off.
If the QMX3 room sensor is present, the selectable time bands
are: Comfort, Precomfort, Reduced, Protection whose
corresponding room temperatures are set to Parameters->
Room unit data n->
If the time slots are different for each day of the week, you
need to set them as described above for every day.
If the time slots are the same as those set for the first day,
you can copy the others, as explained above.
Once the time programme is completed, simply activate it by
setting Parameters->Zone n->Action = Automatic.

6.11 - Cooling circuits time setting

At the first access of the menu Parameters->Zones->Cool
Timer program anomalous default times will result. In order to
restore consistent values, select Reset = Yes. Then proceed to
fill in the weekly program in the same way as in Section 6.10.
If there is no room sensor, the selectable time bands are:
Comfort (on) or Off.
If the QMX3 room sensor is present, the selectable time bands
are: Comfort, Precomfort, Reduced, Protection whose
corresponding room temperatures are set to Parameters->
Room unit data n->.