Figure 6-2 UPS copper bar layout and specifications (unit: mm)
(1) Battery wiring busbar
(4) Output wiring busbar
If multiple UPSs are connected in parallel, input and output power cables as well
as copper bars for each UPS should have the same length and specifications.
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference.
Table 6-2 Recommended cross-sectional areas for power cables
Item
Mains input
Issue 01 (2020-11-30)
NO TICE
Mains input current
(A)
Recommende
d cross-
sectional area
2
(mm
)
Copyright © Huawei Technologies Co., Ltd.
(2) Mains input wiring busbar (3) Bypass input wiring busbar
(5) PE wiring busbar
400 kVA
743
L1
2 x (4 x
240)
L2
L3
6 Installation
500 kVA
600 kVA
929
1115
3 x (4 x
4 x (4 x
240)
185)