Annual Maintenance; Lead-Acid Battery Maintenance - Huawei UPS5000-H Series User Manual

100 kva power module
Hide thumbs Also See for UPS5000-H Series:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Check Item
Parameter
configuration
Status record
Shallow
discharge test
(recommende
d)

8.1.3 Annual Maintenance

Table 8-3 Annual maintenance
Check Item
Grounding
Power cables and
terminals (between the
UPS and the power
distribution cabinet)
Cables and circuit
breaker through-current
capacity

8.2 Lead-Acid Battery Maintenance

Issue 01 (2020-11-30)
Expected Result
The configuration of the
output voltage grade,
frequency, number of
batteries, and battery capacity
meets requirements.
Record the three-phase load
rate and output power factor.
Conduct a shallow discharge
test when the UPS is backed
up to verify that the batteries
can discharge normally.
Expected Result
Check that the ground
cables are connected
securely.
The insulation layer of
cables is intact and
terminals are free from
black marks and
noticeable sparks.
The circuit breakers and
cables meet load
requirements.
The actual cable
through-current capacity
is greater than the circuit
breaker specifications.
Copyright © Huawei Technologies Co., Ltd.
8 Routine Maintenance
Troubleshooting
Reset the parameters.
If an exception occurs, check
the load status.
If an alarm is generated, refer
to the alarm list.
Troubleshooting
Tighten the screws.
● Replace the cables.
● Secure the output
terminals.
● Replace the circuit
breaker.
● Replace the cable.