Huawei UPS5000-H Series User Manual page 109

100 kva power module
Hide thumbs Also See for UPS5000-H Series:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Item
Frequency
Voltage
distortion
Power factor
Transfer
time
(normal)
Output
voltage
imbalance
Overload
capability
Issue 01 (2020-11-30)
400 kVA
● In normal mode, the frequency is synchronous with the
bypass input frequency.
● In battery mode, the frequency is 50 Hz/60 Hz with a
tolerance of ±0.05%.
● Linear load THD < 1% (50–100% load balancing)
● Non-linear load THD < 3% (50–100% load balancing)
1
● Uninterruptible transfer: 0 ms
● Interruptible transfer: < 5 ms
100% unbalanced load voltage imbalance: ±1%
Phase imbalance: 120±1° (balanced load), 120±2° (unbalanced
load)
Inverter overload capability:
● 105% < load ≤ 110%: transfers to bypass mode after 60 min
or longer (ambient temperature ≤ 30°C)
● 100% < load ≤ 110%: transfers to bypass mode after 60 min
or longer (ambient temperature > 30°C)
● 110% < load ≤ 125%: transfers to bypass mode after 10
minutes or longer (10±0.1 minutes)
● 125% < load ≤ 150%: transfers to bypass mode after 1 minute
or longer
● Load > 150% or a short circuit occurs: transfers to bypass
mode after 200 ms or longer
Bypass overload
capability:
At 40°C:
● 110% load: 60
minutes
● 125% load: 10
minutes
● 150% load: 1
minute
● Load > 150%: 100
ms
Copyright © Huawei Technologies Co., Ltd.
10 Technical Specifications
500 kVA
600 kVA
Bypass overload
Bypass overload
capability:
capability:
● At 30°C, load
● At 25°C, load ≤
≤ 135%: runs
for a long
time
● Load > 1000%:
● At 40°C, load
≤ 125%: runs
for a long
time
● Load >
1000%: 100
ms
125%: runs for a
long time
100 ms
102