D Power Cable Specifications - Huawei PDU8000 User Manual

Ups power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 UPS Power Distribution Cabinet
User Manual
Table D-1
Table D-1 Power cable specifications
Wiring
Terminal
Power input
(L/N)
Power input
(PE)
AC output
(L)
AC output
(N/PE)
Issue 01 (2016-03-04)
D
Power Cable Specifications
describes the power cable specifications.
Rated
Current
160 A
250 A
400 A
630 A
160 A
250 A
400 A
630 A
< 10 A
10 A ≤ I ≤ 40
A
40 A < I ≤ 63
A
< 10 A
10 A ≤ I ≤ 40
A
40 A < I ≤ 63
A
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cable
Terminal/Bolt
Diameter
Specifications
2
50 mm
DT-M10
2
95 mm
DT-M12
2
185 mm
DT-M12
2
2 x 185 mm
DT-M12
2
25 mm
DT-M10
2
50 mm
DT-M10
2
150 mm
DT-M12
2
2 x 120 mm
DT-M12
2
Cord end
2.5 mm
terminal (plug
depth 8–12 mm)
2
6 mm
Cord end
terminal (plug
depth 8–12 mm)
2
10 mm
Cord end
terminal (plug
depth 8–12 mm)
2
2.5 mm
OT-M6
2
6 mm
OT-M6
2
10 mm
OT-M6

D Power Cable Specifications

Recommended
Torque
26–33 N•m
46–58 N•m
46–58 N•m
46–58 N•m
26–33 N•m
26–33 N•m
46–58 N•m
46–58 N•m
1.5–1.8 N•m
1.5–1.8 N•m
1.5–1.8 N•m
4.9 N•m
4.9 N•m
4.9 N•m
64

Advertisement

Table of Contents
loading

Table of Contents