UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Figure 7-1 Settings Wizard
Step 2 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. Other
alarms need to be handled.
Step 3 If the system has connected to the remote EPO switch, you need to choose
Monitoring > UPS System > Running Parameter > System Settings on the
WebUI and set EPO detection to Enable.
Step 4 View the system running status diagram on the LCD to check that the UPS is
working in bypass mode.
----End
Issue 01 (2020-11-30)
NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
Contact Set. Check that the connected dry contacts have been enabled and that the
disconnected dry contacts have been disabled.
Copyright © Huawei Technologies Co., Ltd.
7 System Commissioning
70