Appendix
A
Power Cable Specifications
YJV5 cables are recommended. The conduct working temperature is 90°C, and the ambient
temperature is 40°C. The following table describes the specifications.
Port
Description
Current (A)
Power input (L/N)
Power input (PE)
10 ≤ I ≤ 40
AC output (L)
40 < I ≤ 63
10 ≤ I ≤ 40
AC output (N/PE)
40 < I ≤ 63
For more information, refer to the channels provided on the next page.
Rated
Cable Diameter
(mm² )
160
50
200
70
250
95
400
185
630
2x185
160
25
200
35
250
50
400
95
630
2x95
< 10
2.5
6
10
< 10
2.5
6
10
Terminal/Bolt
Specifications
DT-M10
DT-M12
DT-M12
DT-M12
DT-M12
DT-M10
DT-M10
DT-M10
DT-M12
DT-M12
Cord end terminal
(insertion depth: 8–12 mm)
Cord end terminal
(insertion depth: 8–12 mm)
Cord end terminal
(insertion depth: 8–12 mm)
OT-M6
OT-M6
OT-M6
55
16
Recommended
Torque (N· m)
27
47
47
47
47
27
27
27
47
47
1.6
1.6
1.6
4.5
4.5
4.5