7.6.2.2 Performing a Capacity Test

Issue 01 (2020-11-30)
On the home screen of the LCD, choose System Info > Settings > Battery
Settings and set Sched. shallow dis. test to Enable.
Set Sched. shallow dis. test time and Sched. shallow dis. test interval as
required. After setting is complete, the system will perform an automatic
shallow discharge test based on the settings.
On the home screen of the LCD, choose System Info > Maintenance >
Battery Maint.
Tap Start on the right of Shallow Dis. Test to start a shallow discharge test.
Figure 7-12 Starting a shallow discharge test
NO TE
When the battery test is completed normally, the test data is used as common test
data. Record the data obtained from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
● The battery discharge capacity reaches the specified value (10%–50%, 20% by
default).
● The discharge voltage reaches the warning threshold (calculated in real time).
● The load rate fluctuation exceeds 10%.
● An alarm is generated.