Technical Specifications - Huawei UPS5000-H Series User Manual

100 kva power module
Hide thumbs Also See for UPS5000-H Series:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Table 10-1 Physical specifications
Item
Cabling mode
IP rating
Communication
Dimensions (H x W x
D)
Weight
Table 10-2 Environmental specifications
Item
Operating
temperature
Storage temperature
Humidity
Altitude
Issue 01 (2020-11-30)
10

Technical Specifications

Specifications
Routed in and out from the top
IP20
Supports dry contacts, RS485 ports, and FE ports.
Supports SNMP and Modbus.
2000 mm x 800 mm x 1000 mm
< 800 kg
Specifications
0°C to 55°C
Temperature derating coefficient: not derated at 0°C–
40°C, derated to 0.9 at 41°C–45°C, derated to 0.8 at
46°C–50°C, and derated to 0.7 at 51°C–55°C
–40°C to +70°C
0%–95% RH (non-condensing)
0–1000 m
When the altitude is greater than 1000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.