Table 6-3 Power terminal connection requirements
Port
Mains input
Bypass
input
Battery
input
Output
PE
Equipotenti
al ground
point
Table 6-4 Recommended input/output circuit breakers
Component
Name
Mains input
circuit breaker
Bypass input
circuit breaker
Downstream
output circuit
breaker
a: recommended model when the short-circuit current where the circuit breaker
is located is less than 65 kA

6.1.4 Unpacking

Issue 01 (2020-11-30)
Connection
Method
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
Specifications
(400 kVA)
1000 A/3P
800 A/3P
800 A/3P
NO TE
● The input circuit breakers recommended are for reference only.
● If multiple loads are connected, use recommended specifications for branch circuit
breakers.
● The circuit breaker selection principle is to protect loads and cables, and the cascading
principle is to achieve specific protection.
Copyright © Huawei Technologies Co., Ltd.
Bolt
Bolt Length
Specifications
M16
55 mm
M16
55 mm
M16
55 mm
M16
55 mm
M12
30 mm
M6
12mm
a
Specifications
kVA)
1250 A/3P
800 A/3P
800 A/3P
6 Installation
Torque
120 N·m
120 N·m
120 N·m
120 N·m
47 N·m
4.5N·m
a
(500
Specifications
(600 kVA)
1600 A/3P
1000 A/3P
1000 A/3P
a