Monthly Maintenance; Quarterly Maintenance - Huawei UPS5000-H Series User Manual

100 kva power module
Hide thumbs Also See for UPS5000-H Series:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)

8.1.1 Monthly Maintenance

Table 8-1 Monthly maintenance
Check Item
Operating
environment
Power grid
environment
Information
on the LCD

8.1.2 Quarterly Maintenance

Table 8-2 Quarterly maintenance
Check Item
Cleanliness
Issue 01 (2020-11-30)
Expected Result
● Ambient temperature: 0–
40°C
● Humidity: 0–95% RH (non-
condensing)
● Rodent-proof measures
have been taken for the
equipment room.
● The equipment room is
airtight.
● Input voltage: 380 V AC,
400 V AC, or 415 V AC (line
voltage)
● Output voltage: 380 V AC,
400 V AC, or 415 V AC
(tolerance ± 1%, line
voltage)
● Frequency: 40–70 Hz
The status icons on the LCD
indicate that all units are
operating properly, all
operating parameters are
within their normal ranges,
and no fault or alarm
information is displayed.
Expected Result
Wipe the cabinet surface using
a white paper and the paper
does not turn black.
Copyright © Huawei Technologies Co., Ltd.
8 Routine Maintenance
Troubleshooting
● If the humidity or
temperature is abnormal,
check the air conditioner
status.
● Put rodent-proof baffle
plates at the door of the
UPS equipment room.
● Check that the equipment
room is airtight and not in
a direct ventilation
environment.
● If the input voltage is
abnormal, check the power
grid status and input cable
connection.
● If the output voltage is
abnormal, check the UPS
running status and check
whether an alarm is
generated.
If an alarm is generated,
rectify the fault by checking
the device status and
parameters.
Troubleshooting
Remove the dust, especially
from the air filter on the front
door, or replace the air filter.
89

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-h-400 kvaUps5000-h-500 kvaUps5000-h-600 kva

Table of Contents