6.3.4 Connecting a Remote EPO Switch

● Huawei does not provide the EPO switch or cable. Prepare them by yourself.
● Equip the EPO switch with a protective cover to prevent misoperations, and
● Triggering EPO will shut down the rectifier, inverter, charger, and static bypass,
Connect the EPO switch to the dry contact on the UPS using a cable.
Issue 01 (2020-11-30)
NO TICE
The recommended cable is 22 AWG.
protect the cable with a protective tube.
but will not disconnect the UPS mains input. To power off the UPS completely,
turn off the upstream input switch when you trigger EPO.