Powering On Loads; Optional) Setting Parameters For The Bcb Box - Huawei UPS5000-H Series User Manual

100 kva power module
Hide thumbs Also See for UPS5000-H Series:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Figure 7-3 Starting the inverter
----End

7.1.3 Powering On Loads

Procedure
Step 1 After the inverter starts, the UPS works in normal mode. The Bypass mode alarm
on the LCD disappears. Check that the UPS works in normal mode on the System
Status screen of the LCD.
Step 2 Choose System Info > Runn. Info > AC Output on the LCD and check that the
UPS three-phase output voltage and frequency are normal. Use a multimeter to
check that the valid three-phase output voltage and frequency are normal.
Step 3 After confirming that the battery string is properly connected, switch on the
battery string input circuit breaker. If there are multiple battery strings, switch on
the circuit breaker for each battery string and then the general circuit breaker
between the battery strings and the UPS. The No battery alarm on the LCD
disappears.
Step 4 Turn on the downstream output switch to supply power to loads.
----End

7.1.4 (Optional) Setting Parameters for the BCB Box

Prerequisites
A BCB box is installed.
Procedure
Step 1 Choose System Info > Settings > Dry Contact Set, set MUE05A connection to
Enable, and set BCB connection [OL] and Battery breaker [STA] to Enable.
Issue 01 (2020-11-30)
NO TE
If the power module receives a startup command when it cannot be started, the startup
command will be retained for 1 minute. Within 1 minute, if there is no situation (for
example, the power module encounters other faults, executes a shutdown command, or a
fault is rectified) that requires the startup command to be cleared and the power module
becomes able to start, then the power module responds to the startup command.
Copyright © Huawei Technologies Co., Ltd.
7 System Commissioning
72

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-h-400 kvaUps5000-h-500 kvaUps5000-h-600 kva

Table of Contents