UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Item
Rated voltage
Voltage range
Rated frequency
Frequency range
Power factor
Harmonic
current
Table 10-6 Bypass input electrical specifications
Item
Power system
Rated voltage
Rated
frequency
Frequency
range
Input mode
Issue 01 (2020-11-30)
Specifications
380 V AC/400 V AC/415 V AC (line voltage)
0–30°C: not derated at 323–485 V AC, derated from 100%
load to 45% load at 323–191 V AC, and derated from 45%
load to 35% load at 191–138 V AC
30–40°C: not derated at 342–485 V AC, derated from 100%
load to 45% load at 342–191 V AC, and derated from 45%
load to 35% load at 191–138 V AC
50 Hz/60 Hz
40–70 Hz
> 0.99 (full load); > 0.98 (half load)
● THDi < 9% (30% linear load), THDi < 6% (50% linear
load), THDi < 3% (100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-
linear load), THDi < 5% (100% non-linear load)
NOTE
1. The preceding specifications are met when the mains input
and bypass input share a power source.
2. The input THDu is less than 2%.
Specifications
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
50 Hz/60 Hz
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz,
±2 Hz by default)
The mains input and bypass input share a power source (by
default) or use different power sources.
Copyright © Huawei Technologies Co., Ltd.
10 Technical Specifications
100