Ex-relevant data for operation in zones 2, 21 and 22

5 Ex-relevant data for operation in zones 2, 21 and 22
5.1

Electrical connection

5.1.1

Sensor and transmitter in zone 2 or outside of the Ex-area

Models 406012/1-1, 406013/1-1, 406015/1-1. 406016/1-1, 406012/2-1 or 406015/2-1 with 406018/2-1 or with
406018/2-0, 406013/2-1 or 406016/2-1 with 406019/2-1 or with 406019/2-0
HART protocol, PROFIBUS-PA, FOUNDATION Fieldbus
A = Transmitter, B = Sensor
Voltage supply
Alternating voltage (AC)
Termi-
Function
nal
L
Phase
N
Neutral conductor
PE
Protection conductor (PE)
Signal cable connection (for devices with remote mount design type only)
Termi-
Function
nal
M1
Magnet coil
M2
Magnet coil
D1
Data line
D2
Data line
SE
Shielding
E1
Signal line
1S
Shield of E1
E2
Signal line
2S
Shield of E2
3
Measurement potential
Ex-zone 2
Direct voltage (DC)
Termi-
Function
nal
1+
+
2-
-
PE
Protection conductor (PE)
Wire color
Brown
Red
Orange
Yellow
-
Violet
-
blue
-
Green
Outside the Ex-area