Jumo Flowtrans Mag S/H - Compact Design; Atex/Iecex Zone 1; Atex/Iecex Zone 2 - JUMO flowTRANS MAG S Series Safety Manual

Electromagnetic flowmeter for the process industry and hygienic applications
Table of Contents

Advertisement

2.4

JUMO flowTRANS MAG S/H - compact design

Sensor and transmitter form a mechanical unit.
2.4.1

ATEX/IECEx Zone 1

JUMO flowTRANS MAG S01/S02
406012/1-1 (Ex-protection zone 1)
406013/1-1 (Ex-protection zone 1)
Transmitter: dual-compartment housing
Sensor: aluminum housing
ATEX certificate: FM15ATEX0025X
DN 3 to 300: II 2G Ex d e ia ma IIC T6... T2 Gb
> DN 300:
II 2 D Ex ia tb IIIC T70°C... T
IECEx certificate: FME 15.0006X
DN 3 to 300: Ex d e ia ma IIC T6... T2 Gb
> DN 300:
Ex ia tb IIIC T70°C... T
2.4.2

ATEX/IECEx Zone 2

JUMO flowTRANS MAG S01/S02
406012/1-1 (Ex-protection zone 2)
406013/1-1 (Ex-protection zone 2)
Transmitter: single-compartment housing
Sensor: aluminum housing
ATEX certificate:
FM15ATEX0024X:
II 3 G Ex nA mc IIC T4... T3 Gc
FM15ATEX0025X:
II 2 D Ex tb IIIC T70° C... T
IECEx certificate: FME 15.0006X
Ex nA mc IIC T4... T3 Gc
Ex tb IIIC T70° C... T
II 2G Ex d e ia IIC T6...T2 Gb
Db
Medium
Ex d e ia IIC T6... T2 Gb
Db
Medium
Db
Medium
Db
Medium
2 Device versions
JUMO flowTRANS MAG H01/H02
406015/1-1 (Ex-protection zone 1)
406016/1-1 (Ex-protection zone 1)
Transmitter: dual-compartment housing
ATEX certificate: FM15ATEX0025X
II 2G Ex d e ia ma IIC T6... T2 Gb
II 2 D Ex ia tb IIIC T70°C... T
IECEx certificate: FME 15.0006X
Ex d e ia ma IIC T6... T2 Gb
Ex ia tb IIIC T70°C... T
JUMO flowTRANS MAG H01/H02
406015/1-1 (Ex-protection zone 2)
406016/1-1 (Ex-protection zone 2)
Transmitter: single-compartment housing
ATEX certificate:
FM15ATEX0024X:
II 3 G Ex nA mc IIC T4... T3 Gc
FM15ATEX0025X:
II 2 D Ex tb IIIC T70° C... T
IECEx certificate: FME 15.0006X
Ex nA mc IIC T4... T3 Gc
Ex tb IIIC T70° C... T
Medium
Db
Medium
Db
Medium
Db
Medium
Db