3.1.4

Turning the LCD display

Depending on the installation position, the LCD display or transmitter housing can be rotated to allow for
horizontal read-off.
(1)
Transmitter with LCD display
(2)
Housing for transmitter plug-in module
(3)
Rotation lock
1. Switch off voltage supply.
2. Remove case lid see chapter 3.1 "Notes on opening and closing the housing", page 19.
3. Slightly pull back the rotation lock (3) and rotate the transmitter plug-in module with LCD display (1)
to the left or right by 90° until the rotation lock (3) locks back into place.
4. Relocate the case lid and screw down tightly before re-starting.
3.2

Cable inlets

(1)
Cable fittings
(2)
Closures in the terminal box
(3)
Black plugs
The cable fittings supplied are ATEX or IECEx certified.
The black plugs in the cable fittings are intended to provide protection during transport.
All unused cable inlets must be sealed prior to startup, using the seals supplied that are provided in the
terminal box.
Using standard cable fittings and seals is prohibited.
The outer diameter of the connecting cable must be between 6 mm (0.24") and 12 mm (0.47") to ensure
the necessary leak-tightness.
Make sure that the cable fittings and seals are mounted correctly and are leak-tight.
Dual-compartment housing
( ) 1
( ) 3
( ) 2
Single-compartment housing
3 Mounting
(1) (3) (2)
G00759-01
21