Basic Line Filter For Active Line Modules With Active Interface Module; Description; Safety Information - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Connection Booksize

2.5 Basic Line Filter for Active Line Modules with Active Interface Module

2.5
Basic Line Filter for Active Line Modules with Active Interface Module
2.5.1

Description

Basic Line Filters are mainly effective in the frequency range from 150 kHz to 30 MHz; this is
the range relevant to ensure compliance with the appropriate standard.
Boundary conditions of Basic Line Filters for Active Line Modules with Active Interface
Module:
The Basic Line Filters can be used in accordance with the following general conditions for
ensuring CE conformity with regard to cable-borne interference:
● The machine/system must only be used in industrial networks.
● No. of axes ≤12.
● In conjunction with an Active Interface Module, they are designed for use in systems with
● The Basic Line Filters are only suitable for connection to TN systems; otherwise an
2.5.2

Safety information

Line filters are only suitable for direct connection to TN systems.
Basic Line Filters 55 kW, 80 kW and 120 kW must only be used in conjunction with an
Active Interface Module.
A ventilation clearance of 100 mm above and below the components must be observed.
This prevents thermal overloading of the filter.
The input and output connections/terminals must not be interchanged:
Incoming line cable to LINE L1, L2, L3 and
outgoing cable to line reactor at LOAD L1´, L2´, L3´
The line filter may be damaged if this is not observed.
46
a maximum total cable length of 350 m (shielded) in category C2 and 1000 m (shielded)
in category C3.
isolating transformer will be required.
CAUTION
WARNING
WARNING
WARNING
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Booksize Power Units

Advertisement

Table of Contents
loading

Table of Contents