4.4.3.13. Set back to factory settings
You can return to the factory settings by using the parameter 62
Rinnai
made on the mainboard will be lost and returned to the initial values.
4.4.4. About Cascade System Setup
4.4.4.1.
Synchronising the boiler local clocks in a cascade system
Assume that you have set the clock time to 15:50 when comissioning the master boiler. In order to
synchronise the sl
Engineer
LPB system.
Set the parameter (6640) of the master
4.4.4.2.
Cascade master boiler selection, cascade sensor usage
The cascade sensor seems like to be used in case of a cascade system setup but as reference to Section
2.4.5, it is mounted on the hydraulic header or on the pipeline after the plate heat exchanger as a strap-on
sensor. As underlining, in your boiler sanitary installation
Rev: RINNAI Service manual (English)
Date:14/05/2019
clocks with the master:
88