The bell symbol is being displayed. When I press the Info button I read the
the error code "332: Sensor input BX3 without function".
Answer:
As a first comment, it should be known that a sensor which is not assigned to any function may be existing
on the system. Enter the line 5931 (BX2) in the Configuration menu. If BX2 is not being used, set this
parameter's value to "None". Following this, save the sensors via the parameter 6200 in the configuration
menu. If the problem still exists, try substituting or shifting the multifunctional sensor inputs. Example:
Using BX3 instead of BX1, using BX2 instead of BX2 etc.
I c
parameter 8327 ?
Answer:
Parameter 8327 only displays the pressure value read for dynamic pressure supervision. Otherwise, no
value will be displayed. If you like to display the dynamic pressure
parameter [4195.1] in the Engineer menu. This adjustment can be made by using ACS 420.
In normal operation, you can display the static pressure (which you want to know is this) via the parameter
9005
|
Water pressure H1
reset. What should I do?
Answer:
This error occurs because the permitted water pressure in the system passes the upper limit. Firstly you
have to learn the water pressure as the way expressed below:
Engineer
Diagnostics Consumer
Let the read value be 4,4 bar. Check the maximum water pressure set value that you have adjusted in your
system. Go to Engineer
Let the read value be 4 bar (maximum water pressure). In such a case, you will get the high pressure
warning error. Similarly
minimum water pressure by Engineer
If the system water pressure if out of the region bordered by the parameters 6140 and 6141, you will notice
a water pressure error. In a field application, you can get rid of the problem by adjusting the values for the
minimum and maximum water pressure values. In order to be able to change these values, you must enter
Rev: RINNAI Service manual (English)
Date:14/05/2019
9005
Configuration
6140 (maximum water pressure).
Configuration
6141 (minimum water pressure).