You may face with this error while the commissioning of the devices. The waiting delay period is 6 minutes.
The error will dissappear itself if there is no connection mistake or malfunction.
displayed for one of the LMS 14 control cards consisting of 3 boilers. The
killing code is 625 for this error. How can I get rid of the so called error?
Answer:
Safety time for establishment of flame exceeded is displayed in a case of delay for the appearance of the
flame which passes the safety time.
The combustion process occurs with a sequence as in the graph above. The gas valve opening and ignition
of the fuel/air mixture occurs in the safety time (TSA). The ignition should have been occured beneath this
period. If the combustion does not stably continue and the flame is not stable after the ignition, the flame
will be lost and the so called error will be displayed. The boiler will try for 4 times to ignite the fuel/air
mi
needed in this case.
[3633.1]
|
Max StartAttemps TSA | 4
How can a swimming pool mixing circuit can be controlled via the LMS 14
control panel ?
Rev: RINNAI Service manual (English)
Date:14/05/2019
Answer:
Connect the pump of the pool to an appropriate relay
Set the value of the parameter 5950 in the
The QX 1 relay is free as a factory setting. Connect the
pool pump to this relay. You must use a contacter for
high electrical current pumps. Through the goal, set the
value of the possible selections for QX1 in the
pool pump Q1
124
lock out
Release swi pool source heat