This is the composite temperature that is referenced in this chapter. The composite value flows
as a mean of the real outside temperature plus the attenuated outside temperature. It is better
to check the graph below.
4.4.3.4.
Room influence and Room Thermostat
The room temperature is used by the LMS 14 for a measure of influencing the mean (or sensed)
outside temperature (composite temperature) for decision making by the room influencing
parameters. There are 3 parameters for different direct circuits. The unit is percentages (%) and
the value range is 1-100.
750 | RmTmp gain factor ID1 for heating circuit 1
1050 | RmTmp gain factor ID2 for heating circuit 2
1350 | RmTmpAuthority ID3/P for heating circuit 3
Setting
Type of compensation
---- %
Weather compensation alone (*)
1...99 %
Weather compensation with room influence (*)
100 %
Room compensation alone
(*) Outside temperature sensor required.
4.4.3.5.
Heating curve
If you have difficulties regarding the heating inside the rooms even you increase the confort
Rev: RINNAI Service manual (English)
Date:14/05/2019
71
heating circuit.